Trouble Shooting Guide
SYMPTOM POSSIBLE CAUSE PROCEDURE
Unit doesn't run 1. No power to unit 1. Plug in unit
2. Temperature control turned off 2. Check temperature control
3. Temperature control faulty 3. Test temperature control
4. Compressor overheated 4. Clean condenser coil/filter
5. Condenser fan faulty 5. Service condenser fan
6. Overload protector faulty 6. Test overload
7. Compressor relay faulty 7. Test relay
8. Compressor faulty 8. Call ASA for service
Unit short cycles 1. Condenser coil/filter dirty 1. Clean coil/filter
2. Pressure control settings 2. 30 cut in / 15 differential
3. Condenser fan faulty 3. Service fan and motor.
4. Compressor faulty 4. Call ASA for service
5. Overload repeatedly tripping 5. Check outlet voltage
6. Solenoid not seating 6. Call ASA for service
Unit runs constantly 1. Condenser coil/filter dirty 1. Clean coil/filter
2. Condenser fan faulty 2. Service condenser motor
3. Pressure control settings 3. 30 cut in / 15 differential
4.. Filter light on 4.. Clean/change condenser filter
Unit not cold enough
1. Temperature control set too
high 1. Adjust control to lower setting
2. Temperature control faulty 2. Test control
3. Condenser coil/filter dirty 3. Clean coil/filter
4. Filter light on 4. Clean/change condenser filter
5. Air flow
5. Allow 3” space on right end of
unit for ventilation
6. Refrigerant leaking or
contaminated
6. Call ASA for service
Unit too cold 1. Temperature control set too low 1. Adjust control to raise setting
2. Temperature control faulty 2. Test control
Dixell control errors 1. Flashing “HA” 1. High Alarm error
2. Flashing “P1” 2. Primary probe failure
3. Flashing “P2” 3. Secondary (defrost) probe failure
Unit noisy
1. Compressor mountings loose or
hardened.
1. Tighten or replace compressor
mountings
2. Condenser fan damaged or
hitting fan shroud
2. Inspect condenser fan
Filter light
1. Light on. 1. Clean/replace filter
2. Air flow
2. Allow 3” space on right end
of unit for ventilation